Heat Alarm & Detector Test Tunnel

Function:
-
Well Tuned PID Temperature Control
-
EN 54-5 Full Standard Test Function
-
Sound detection, automatic recording
-
Controlled Temperature precisely
Equipment Function:
The heat alarm & detector test tunnel is used to test directional dependence, static response temperature, response times test for fire alarm and detector.
The equipment meets the requirements of GB4716, EN 54-5, BS 5446-2 and ISO standards.
The standard test tunnel is composed of tunnel, heater, Chiller, temperature control system, computer etc. According to the requirements of standard specifications and parameters, we use fast response thermocouples and advanced PID controller to attain the heating rate of 0.2 ℃/min, 1 ℃/min, 3 ℃/min, 5 ℃/min, 10 ℃/min, 20 ℃/min and 30 ℃/min as standard required.
The maximum temperature is up to 160 ℃. During the test, the temperature will be controlled at + / – 2 ℃.
The specially developed Zomtest heat test tunnel software can automatically control the test process, record the temperature curve and record the alarm response time.
Technical Detail of Standard Test Tunnels for factory:
| Model No. | ZNEN54-5HC |
| Applicable Products | Heat alarm, Heat detectors |
| Application | Factory R&D test, FPC audit test, |
| Standards | BS 5446-2, EN 54-5, GB 4716 |
| Capacity | One sample |
| Test tunnel | 2.1m x 0.5m x 1.1m, Test section size 430mm x 270mm |
| Power supply | 380VAC power:20 kW |
| Temperature control | PID setting value +/-2℃ |
| Temperature rise rate | 0.2° C/min、 1°C/min、3°C/min、5°C/min、10°C/min、20°C/min、30°C/min |
| Temperature range | 5~160°C |
| Air speed | 0.0~1.2 m/s |
| Test items | 1)、Directional dependence 2)、Static response temperature 3)、Response times from typical application temperature 4)、Response times from 25°C 5)、Response times from high ambient temperature (dry heat operational) 6)、Supply voltage test 7)、Other tests(need additional equipment) |